Model: SXHSL630R Specifications |
Voltage Rating |
120/230 Volts Split Phase |
Load Rating |
30 Amps at 208 Volts |
Voltage Protection Rating |
800V Line - Line 500V Line - Ground |
Input Connector |
NEMA L6-30P |
Output Connector |
NEMA L6-30R |
Attenuation |
Normal Mode: >30dB 80kHz -50MHz
Common Mode: >30dB 200kHz -50MHz |
Power Requirement (no load) |
6 Watts |
Under-Voltage Shutdown |
Adjustable from 140 Volts to 170 Volts, or Disabled. Restores at 190 Volts |
Over-Voltage Shutdown |
Adjustable from 260 Volts to 300 Volts.
Restores at 250 Volts |
Response Time |
100msec Over-Voltage
150msec Under-Voltage |
Under-Voltage Record Event Definition |
AC voltage has dropped below 180V |
Over-Voltage Record Event Definition |
AC voltage has risen above 260V |
Power Outage Event Definition |
AC voltage has dropped below 20V |
Voltmeter Accuracy |
Peak reading type. Typical product accuracy is ±2% between 100V and 300V |
Internal Memory Capacity |
60 Events with timestamp
999 counts of each event type |
Timestamp accuracy |
±2.5% |
Data Interface |
XG-PCS-IK
Custom USB –RJ25 |
Computer Requirements |
For use with Diagnostic Software. Minimum 133MHz Pentium processor (or equivalent), minimum 64MB of RAM, minimum 10MB free hard drive space, VGA or higher resolution monitor, keyboard, mouse, CD or DVD drive, minimum screen resolution of 1024x768, Microsoft Windows 2000/XP/Vista/7 |
Dimensions |
17" W x 10.670" D x 3.350" H (2 RU) |
Weight |
15 lbs |
BTU/h |
100 BTU/h Maximum at full rated load |
Temperature Range |
5°C to 40°C |
Humidity Range |
5% to 95% R.H. Non-condensing |
Agency Listings |
ETL Certified to UL 1449
ETL Certified to CSA C22.2 No. 8-M1986
(R2008) |
Warranty |
Limited lifetime and limited five years connected protection warranty |