Model: SX1115RT Specifications |
Load Rating |
15 Amps @ 120 volts |
Power Requirements (no load) |
15 watts |
Surge Let-Through Voltage (6000-volt surge) |
0 volts |
UL 1449 Adjunct Classification Test Results |
1000 surges, 6000 volts, 3000 amps, B3 pulse |
Measured suppressed voltage |
170 volts, no failures |
Federal Guidelines |
Grade A, Class 1, Mode 1 (CID A-A-55818) |
EMI/RFI Filter, Normal Mode (50-ohm load) |
40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz |
EMI/RFI Filter, Common Mode (50-ohm load) |
18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz |
Maximum Applied Surge Voltage |
6000 volts* |
Maximum Applied Surge Current |
Unlimited, due to current limiting* |
Maximum Applied Surge Energy |
Unlimited, due to current limiting* |
Endurance (C62.41-1991 Category B3 pulses) |
1 kV>500,000; 3 kV>10,000; 6 kV>1000 |
Undervoltage Shutdown |
90 volts (resume at 100 v) |
Overvoltage Shutdown |
145 volts (resume at 135 v) |
Maximum Load Inrush Current During Power-up |
1000 Joules |
Remote Turn-on Applied Voltage Range |
5 to 30 volts DC |
Contact Closure |
1.5 mA |
5 V DC Applied Voltage |
0.1 mA |
12 V DC Applied Voltage |
1.5 mA |
24 V DC Applied Voltage |
5.0 mA |
Auxiliary Relay Contact Rating |
30 Volts at 1 Amp |
LED Output |
12 volts DC, maximum 20 mA (resistor required) |
Dimensions |
1.75" H x 19" W x 10.5" D (4.5 x 48.3 x 26.7 cm) |
Weight |
11 lbs (5 kg) |
Temperature Range |
5º to 35º C |
Humidity Range |
5% to 95% R.H., non-condensing |
Agency Listings |
ETL and cETL certified to (UL 1449; CSA C22.2 No.8-M1986, R2000) |