Model: SA82 Specifications |
Load Rating |
8 amps @ 120 volts |
Power Requirement (no load) |
10 watts |
UL 1449-2 Adjunct Classification Test Results |
1000 surges, 6000 volts, 3000 amps, C1 pulse, measured suppressed voltage 290 volts, no failures |
Federal Guidelines |
Grade A, Class 1, Mode 1 (CID A-A-55818) A |
EMI/RFI Filter, Normal Mode (50-ohm load) |
40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz |
EMI/RFI Filter, Common Mode (50-ohm load) |
18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz |
Maximum Applied Surge Pulse Joule Rating |
Unlimited, due to current limiting (8 x 20 µs)* |
Maximum Applied Surge Pulse Voltage |
6000 Volts* |
Maximum Applied Surge Pulse Current |
Unlimited, due to current limiting* |
Endurance |
IEEE C62.41-1991 Category B3 (C1) |
Pulses |
1 kv>500,000; 3 kv>10,000; 6 kv>1000 |
Overvoltage Shutdown |
145 Volts (resume at 135 volts) |
Dimensions |
1.75" H x 5.31" W x 9.06" D |
Weight |
3.4 lbs |
Temperature Range |
5º to 35º C |
Humidity Range |
5% to 95% R.H., non-condensing |
Agency Listings |
ETL and cETL certified to (UL 1449;
CSA C22.2 No.8-M1986, R2000)
ETL Certified to UL 1283 |
CE |
- |
FCC |
- |