Model: SXBDLUPS2000 Specifications |
UPS2000OL Stand Alone Battery Backup |
Voltage |
120 VAC (80 - 138 V at 100% load) 60-138 V at 40% load |
Capacity VA (W) |
2000 VA (1400 W) |
Frequency |
50/60 Hz auto sensing |
Power Factor |
≥ 0.97 |
Topology |
True on-line, Double conversion, Input PF correction |
Voltage |
120 VAC |
Wave Form |
Sine wave, zero transfer time |
Load Power Factor |
0.7 |
Efficiency AC/DC/AC |
≥ 90% |
Auto Restart |
Yes |
Start on Battery |
Yes |
Rated Current |
16.6 A |
Overload Capacity |
110-150% for 30 sec, ≥ 150% for 200msec |
Crest Factor |
3:1 at full load |
Battery Type (UPS) |
(4) 12V 7.2AH/48V |
Backup Time |
7-11 min (internal batteries) to 18 hours using External Battery Packs (EBP) |
Extended Battery Packs |
EBP2 |
Battery Type (EBP) |
2 strings of (4) 12V 7.2AH/48V |
Recharge Time |
Typically < 4 hours |
Unit Dimensions (W x D x H) |
17.3" x 21.7" x 5.2" |
Shipping Dimensions (W x D x H) |
22.3" x 27.4" x 11.0" |
Unit Weight |
79.4 lbs |
Shipping Weight |
91.5 lbs |
Line Cord |
5-20P |
Receptacles |
(1) NEMA L5 - 20R + (4) NEMA 5 - 20R |
Communication Interface |
RS-232 or SNMP (optional card) |
Included in box |
UPSILON CD, horizontal brackets, 5:1 brackets, manual, 6ft DB9 cable |
Operating Temperature |
0 - 40°C (32 - 104°F) |
Audible Noise |
< 50dba at one meter |
Altitude |
6000 ft (1830 m) above sea level |
Warranty |
Three year electronics / Three year batteries |
North America |
UL cUL FCC |
LCD Visual Display |
Input/output voltage & frequency, on-line mode, back up mode, battery capacity, load level |
Audible Alarm |
Beep every 4 sec (on battery) |
UPS Fault |
Continuous beeping sound and LCD display |
SX1120RT Rack Mount Surge Eliminator |
Load Rating |
15 Amps @ 120 volts |
Power Requirements (no load) |
15 watts |
Surge Let-Through Voltage (6000-volt surge) |
0 volts |
UL 1449 Adjunct Classification Test Results |
1000 surges, 6000 volts, 3000 amps, B3 pulse |
Measured suppressed voltage |
170 volts, no failures |
Federal Guidelines |
Grade A, Class 1, Mode 1 (CID A-A-55818) |
EMI/RFI Filter, Normal Mode (50-ohm load) |
40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz |
EMI/RFI Filter, Common Mode (50-ohm load) |
18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz |
Maximum Applied Surge Voltage |
6000 volts* |
Maximum Applied Surge Current |
Unlimited, due to current limiting* |
Maximum Applied Surge Energy |
Unlimited, due to current limiting* |
Endurance (C62.41-1991 Category B3 pulses) |
1 kV>500,000; 3 kV>10,000; 6 kV>1000 |
Undervoltage Shutdown |
90 volts (resume at 100 v) |
Overvoltage Shutdown |
145 volts (resume at 135 v) |
Maximum Load Inrush Current During Power-up |
1000 Joules |
Remote Turn-on Applied Voltage Range |
5 to 30 volts DC |
Contact Closure |
1.5 mA |
5 V DC Applied Voltage |
0.1 mA |
12 V DC Applied Voltage |
1.5 mA |
24 V DC Applied Voltage |
5.0 mA |
Auxiliary Relay Contact Rating |
30 Volts at 1 Amp |
LED Output |
12 volts DC, maximum 20 mA (resistor required) |
Dimensions |
1.75" H x 19" W x 10.5" D (4.5 x 48.3 x 26.7 cm) |
Weight |
11 lbs (5 kg) |
Temperature Range |
5º to 35º C |
Humidity Range |
5% to 95% R.H., non-condensing |
Agency Listings |
ETL and cETL certified to (UL 1449; CSA C22.2 No.8-M1986, R2000) |