Model: SA966 Specifications |
Load Rating |
8 Amps @ 120 Volts |
Power Requirement (no load) |
10 watts |
Surge Let-Through Voltage (6000-volt surge) |
- |
UL 1449 Adjunct Classification Test Results |
1000 surges, 6000 Volts, 3000 Amps, C1 pulse |
Measured suppressed voltage |
290 Volts, no failures |
Federal Guidelines |
Grade A, Class 1, Mode 1 (CID A-A-55818) |
Maximum Applied Surge Pulse Joule Rating |
Unlimited, due to current limiting (8 x 20 µs) |
EMI/RFI Filter, Normal Mode (50-ohm load) |
40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz |
EMI/RFI Filter, Common Mode (50-ohm load) |
18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz |
Maximum Applied Surge Voltage |
6000 Volts* |
Maximum Applied Surge Current |
Unlimited, due to current limiting* |
Maximum Applied Surge Energy |
Unlimited, due to current limiting* |
Endurance (C62.41-1991 Category B3 pulses) |
1 kV>500,000; 3 kV>10,000; 6 kV>1000 |
Dimensions |
3.0" H x 7.5" W x 4.0" D (7.6 x 19.0 x 10.2 cm) |
Weight |
5.4lbs (2.54 kg) |
Temperature Range |
5º to 35º C |
Humidity Range |
5% to 95% R.H., non-condensing |
Agency Listings |
ETL and cETL certified to (UL 1449; CSA C22.2 No.8-M1986, R2000) UL 1283 |