OUTPUT |
Output Volt Amp Capacity (VA) |
2200 |
Output kVA Capacity (kVA) |
2.2 |
Output Watt Capacity (Watts) |
1920 |
Output kW Capacity (kW) |
1.92 |
Power Factor |
0.87 |
Nominal Output Voltage(s) Supported |
220V; 230V; 240V |
Nominal Voltage Details |
230V nominal output in battery mode |
Frequency Compatibility |
50 / 60 Hz |
Frequency Compatibility Details |
Automatic frequency selection |
Output Voltage Regulation (Line Mode) |
-15%, +6% |
Output Voltage Regulation (Battery Mode) |
+/- 5% |
Output Receptacles |
(8) C13 |
Included Output Power Cables |
Includes 3 C13 to C14 output power cables |
Load Management Receptacles |
Two switchable single-outlet C13 load banks |
Hot-Swap PDU options |
PDUBHV20 (2U / 6 C13, 2 C19 outlets) |
Output AC Waveform (AC Mode) |
Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |
INPUT |
Rated input current (Maximum Load) |
10.7A |
Nominal Input Voltage(s) Supported |
230V AC |
UPS Input Connection Type |
C20 inlet |
UPS Input Connection Description |
IEC320-C20 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles |
Input Circuit Breakers |
15A |
Input Phase |
Single-Phase |
BATTERY |
Full Load Runtime (min.) |
5 min. (1920w) |
Half Load Runtime (min.) |
11.9 min. (960w) |
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
External Battery Pack Compatibility |
BP48V24-2U(limit 1); BP48V60RT-3U(multi-pack compatible); BP48V27-2US(multi-pack compatible) |
DC System Voltage (VDC) |
48 |
Battery Recharge Rate (Included Batteries) |
Less than 4.5 hours from 10% to 90% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
RBC94-2U |
Battery Access |
Front panel battery access door |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Expandable Runtime |
Yes |
VOLTAGE REGULATION |
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 158 to 278 |
Overvoltage Correction |
Voltage reduction of 12% applies when input is between 244-278V |
Undervoltage Correction |
Voltage boost of 12% applies when input voltage is between 183-206V |
Severe Undervoltage Correction |
Voltage boost of 24% applies when input voltage is between 158-182V |
USER INTERFACE, ALERTS & CONTROLS |
Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) |
Switches |
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions |
Alarm Cancel Operation |
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available |
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
SURGE / NOISE SUPPRESSION |
UPS AC Suppression Joule Rating |
350 |
UPS AC Suppression Response Time |
Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |
PHYSICAL |
Included Mounting Accessory Description |
4 post rackmount installation accessories included |
Installation Form Factors Supported with Optional Accessories |
2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND) |
Primary Form Factor |
Rackmount |
UPS Power Module Dimensions (hwd, cm) |
8.89 x 44.45 x 49.53 |
Rack Height (U Spaces) |
2 |
Minimum Required Rack Depth (cm) |
67.31 |
UPS Power Module Weight (kg) |
31.18 |
UPS Shipping Dimensions (hwd / cm) |
23.50 x 62.86 x 57.15 |
Shipping Weight (kg) |
37.3 |
Cooling Method |
Fan |
UPS Housing Material |
Steel |
Minimum Required Rack Depth (mm) |
673 |
Primary UPS Height (mm) |
89 |
Primary UPS Width (mm) |
444 |
Primary UPS Depth (mm) |
495 |
Shipping Height (mm) |
235 |
Shipping Width (mm) |
629 |
Shipping Depth (mm) |
572 |
ENVIRONMENTAL |
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
161 |
AC Mode Efficiency Rating (100% Load) |
98% |
COMMUNICATIONS |
Communications Interface |
USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
Network Management Cards |
SNMPWEBCARD; TLNETCARD; WEBCARDLX; RELAYIOCARD |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert |
Communications Cable |
USB, DB9 and EPO cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
LINE / BATTERY TRANSFER |
Transfer Time |
6 ms. (AC to DC) / 1 ms. (DC to AC) |
Low Voltage Transfer to Battery Power (Setpoint) |
158V |
High Voltage Transfer to Battery Power (Setpoint) |
278V |
SPECIAL FEATURES |
Grounding Lug |
Back panel grounding lug |
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
High Availability UPS Features |
Hot swappable batteries |
Green Energy-Saving Features |
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks |
CERTIFICATIONS |
UPS Certifications |
CE |
UPS Certification Details |
IEC 62040-1, IEC 62040-2 Class A EMI, GOST |
WARRANTY |
Product Warranty Period (International) |
2-year limited warranty |
Product Warranty Period (Mexico) |
2-year limited warranty |
Product Warranty Period (Puerto Rico) |
2-year limited warranty |