Output |
Output Volt Amp Capacity (VA) |
1000 |
Output kVA Capacity (kVA) |
1.0 |
Output Watt Capacity (Watts) |
800 |
Power Factor |
0.8 |
Nominal Output Voltage(s) Supported |
110V; 115V; 120V |
Nominal Voltage Details |
120v nominal output in battery mode |
Frequency Compatibility |
60 Hz |
Output Voltage Regulation (Line Mode) |
-21%, +8% |
Output Voltage Regulation (Battery Mode) |
+/- 5% |
Output Receptacles |
(6) 5-15R |
Load Management Receptacles |
Two switchable two-outlet 5-15R load banks |
Output AC Waveform (AC Mode) |
Sine wave |
Output AC Waveform (Battery Mode) |
Pure Sine wave |
Input |
Rated input current (Maximum Load) |
9.2A |
Nominal Input Voltage(s) Supported |
120V AC |
UPS Input Connection Type |
5-15P |
Input Circuit Breakers |
15A |
UPS Input Cord Length (ft.) |
10 |
Recommended Electrical Service |
15A 120V |
Input Phase |
Single-Phase |
Battery |
Full Load Runtime (min.) |
5.3 min. (800w) |
Half Load Runtime (min.) |
15 min. (400w) |
DC System Voltage (VDC) |
24 |
Battery Recharge Rate (Included Batteries) |
Less than 4 hours from 10% to 90% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
See Tripp Lite UPS Replacement battery selector |
Battery Access |
Front panel battery access door |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Expandable Runtime |
No |
Voltage Regulation |
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147 |
Overvoltage Correction |
Input voltages between 128 and 147 are reduced by 12% |
Undervoltage Correction |
Input voltages between 83 and 107 are boosted by 14% |
User Interface, Alerts & Controls |
Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options) |
Switches |
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions |
Alarm Cancel Operation |
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available |
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions |
Surge / Noise Suppression |
UPS AC Suppression Joule Rating |
570 |
UPS AC Suppression Response Time |
Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |
Physical |
Included Mounting Accessory Description |
4 post rackmount installation accessories included |
Installation Form Factors Supported with Optional Accessories |
2 post rackmount(2POSTRMKITWM); Wallmount(2POSTRMKITWM); Tower(2-9USTAND) |
Primary Form Factor |
Rackmount |
UPS Power Module Dimensions (hwd, in.) |
3.45 x 17.35 x 12.5 |
Rack Height (U Spaces) |
2 |
Minimum Required Rack Depth (inches) |
15.5 |
UPS Power Module Weight (lbs.) |
35.4 |
UPS Power Module Weight (kg) |
16.06 |
UPS Shipping Dimensions (hwd / in.) |
9 x 24 x 20.2 |
Shipping Weight (lbs.) |
46.4 |
Cooling Method |
Fan |
UPS Housing Material |
Steel |
Minimum Required Rack Depth (mm) |
394 |
Primary UPS Height (mm) |
88 |
Primary UPS Width (mm) |
441 |
Primary UPS Depth (mm) |
318 |
Shipping Height (mm) |
229 |
Shipping Width (mm) |
610 |
Shipping Depth (mm) |
513 |
Environmental |
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
134 |
Battery Mode BTU / Hr. (Full Load) |
600 |
AC Mode Efficiency Rating (100% Load) |
95% |
Communications |
Communications Interface |
USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
Network Management Cards |
SNMPWEBCARD; TLNETCARD; WEBCARDLX |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert |
Communications Cable |
USB and DB9 cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
Network UPS Tools Compatibility |
NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite |
Line / Battery Transfer |
Transfer Time |
4 milliseconds (AC to battery), 2 milliseconds (Battery to AC) |
Low Voltage Transfer to Battery Power (Setpoint) |
83 |
High Voltage Transfer to Battery Power (Setpoint) |
147 |
Special Features |
Grounding Lug |
Back panel grounding lug |
Cold Start (Startup in Battery Mode During a Power Failure) |
Cold-start operation supported |
High Availability UPS Features |
Hot swappable batteries |
Certifications |
UPS Certifications |
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category B (EMI) |
Product Warranty Period (Worldwide) |
2-year warranty, 3 year with registration. Note: Registration is required for 3-year warranty. |